SQ08-SQ40 Mechanical Installation Manual

Major Alarm

A Major Alarm consists of any of the following situations which cause the Master Relay to open immediately and stop all Dryer functions:

  • Opening of the High-Limit Thermostat due to excessive drying air temperature;
  • Opening of an overload relay contact protecting any Motors, due to an overload or low voltage condition, causing a higher-than-allowable current or amperage flow through the relay contacts.
  • Opening of an overload (if the overload is wired into the system) protecting an auxiliary conveyor motor, due to an overload or low-voltage condition, causing a higher-than-allowable current or amperage flow through the relay contacts;
  • Opening the Rear Plenum Door while the Dryer is operating, causing the Door Safety Switch to shut down the Dryer immediately;
  • Exhaust air (being monitored for temperature) exceeds 210° F [98.89°C], thereby causing the Exhaust Air High Temperature Switch to shut down the Dryer so the cause of the excessive heat can be determined;
  • A momentary power failure.

Lower Plenum RTD and Hi-Limit Sensor

Exhaust Air Temperature Thermostat

(front Bulkhead, looking UP)

Stoppage at Unload

If the Unload Discharge has a heavy enough grain load to clog and trip the Sensor Paddle (see Figure 90) the Trip Lever on the exterior of the Cover will activate and shut down the Dryer unload system.

The Unload Trip Lever is shipped secured with a screw that must be removed before operation.

1

2

3

4

Unload Sensor and Trip Lever

Copyright © 2014-2016 CTB, Inc. All rights reserved  BL0815