Liquid Propane (LP) Fuel Supply Requirements (U.S.)
LP gas fuel tanks of 2000 gallons (water volume) [7 571 L] capacity or less must be installed with the nearest point at least 25' [7.62 m] from the nearest point of the Dryer. LP tanks with a combined volume of 2001 - 30,000 gallons [7 575 - 11 362 L] capacity must be installed with the nearest point at least 50' [15.24 m] or more from the nearest point of the Dryer. This is mandatory per NFPA Bulletin No. 58, Storage and Handling Liquefied Petroleum Gases.
IMPORTANT! LP piping must be Schedule 80 black iron pipe or stronger, connected to the supply line on LP-gas Dryers.
Each LP gas supply tank must have an excess flow valve that has a rated flow less than the flow capacity of the piping from the tank to the Dryer. The piping and excess flow valve design must be installed inside each LP tank and must meet the requirements of NFPA No. 58, Paragraph 3135 (a) (3) current edition in effect at the time of installation. Suggested excess flow valve capacity ratings are 3 - 6 gallons [11.4 - 22.7 L] per minute.
A manual gas shutoff valve must be installed as close to the LP tank as possible, must be at least 25' [7.62 m] away from the Dryer, and readily accessible. Each tank must have a separate shutoff valve. For manifolds connecting parallel tank installations, a main shutoff valve should be installed in the pipe just downstream of the manifold.
IMPORTANT! DO NOT OPERATE the Dryer while the LP tank is being filled—wait for ten minutes after the truck filler hose has been removed
LP gas fuel tank storage should be a minimum of:
An LP fuel tank contains a usable fuel supply of approximately 75% of tank water volume capacity. For example, a 1000-gallon [3 785-L]water-volume tank contains approximately 750 gallons
Copyright © 2014-2016 CTB, Inc. All rights reserved BL0815